Table of Contents
The Advantages of Step-up Transformers in Power Distribution
Step-up transformers are essential components in the electrical power transmission system, designed to elevate voltage levels from power plants to higher voltages suitable for long-distance transmission. By increasing the voltage, these transformers significantly reduce power losses during transportation, ensuring more efficient delivery of electricity to end-users.
One notable feature of step-up transformers is their capacity to handle large loads, such as the 4000 kVA transformers commonly used in industrial and utility applications. Their robust design and high capacity make them ideal for supporting extensive power grids, providing reliable and stable voltage transformation under demanding conditions.
China Enterprise’s High Cost-Performance 4000 kVA Transformer
Chinese enterprises have gained a reputation for producing high-quality, cost-effective electrical equipment, including 4000 kVA transformers. These transformers combine advanced technology with competitive pricing, making them an attractive option for businesses looking to optimize their infrastructure investments.
model | Rating capacity (KVA) | Voltage combination(KV) | Off-load losses(W) | Load losses(W) | Off-load current (%) | Short-circuit impedance (%) |
SCH15-30 | 30 | 6,6.3,6.6,10,11/0.4 | 70 | 710 | 1.6 | 4.0 |
SCH15-50 | 50 | 6,6.3,6.6,10,11/0.4 | 90 | 1000 | 1.4 | 4.0 |
SCH15-80 | 80 | 6,6.3,6.6,10,11/0.4 | 120 | 1380 | 1.3 | 4.0 |
SCH15-100 | 100 | 6,6.3,6.6,10,11/0.4 | 130 | 1570 | 1.2 | 4.0 |
SCH15-125 | 125 | 6,6.3,6.6,10,11/0.4 | 150 | 1850 | 1.1 | 4.0 |
SC(B)H15-160 | 160 | 6,6.3,6.6,10,11/0.4 | 170 | 2130 | 1.1 | 4.0 |
SC(B)H15-200 | 200 | 6,6.3,6.6,10,11/0.4 | 200 | 2530 | 1.0 | 4.0 |
SC(B)H15-250 | 250 | 6,6.3,6.6,10,11/0.4 | 230 | 2760 | 1.0 | 4.0 |
SC(B)H15-315 | 315 | 6,6.3,6.6,10,11/0.4 | 280 | 3470 | 0.9 | 4.0 |
SC(B)H15-400 | 400 | 6,6.3,6.6,10,11/0.4 | 310 | 3990 | 0.8 | 4.0 |
SC(B)H15-500 | 500 | 6,6.3,6.6,10,11/0.4 | 360 | 4880 | 0.8 | 4.0 |
SC(B)H15-630 | 630 | 6,6.3,6.6,10,11/0.4 | 420 | 5880 | 0.7 | 4.0 |
SC(B)H15-630 | 630 | 6,6.3,6.6,10,11/0.4 | 410 | 5960 | 0.7 | 6.0 |
SC(B)H15-800 | 800 | 6,6.3,6.6,10,11/0.4 | 480 | 6960 | 0.7 | 6.0 |
SC(B)H15-1000 | 1000 | 6,6.3,6.6,10,11/0.4 | 550 | 8130 | 0.6 | 6.0 |
SC(B)H15-1250 | 1250 | 6,6.3,6.6,10,11/0.4 | 650 | 9690 | 0.6 | 6.0 |
SC(B)H15-1600 | 1600 | 6,6.3,6.6,10,11/0.4 | 780 | 11730 | 0.6 | 6.0 |
SC(B)H15-2000 | 2000 | 6,6.3,6.6,10,11/0.4 | 1000 | 14450 | 0.5 | 6.0 |
SC(B)H15-2500 | 2500 | 6,6.3,6.6,10,11/0.4 | 1200 | 17170 | 0.5 | 6.0 |
The Chinese manufacturers emphasize durability, efficiency, and ease of maintenance in their transformer designs, which contributes to their high cost performance ratio. As a result, many global companies are turning to Chinese suppliers to meet their large-scale power distribution needs without compromising on quality or exceeding budgets.