Table of Contents
Understanding Distribution Transformers
Distribution transformers are essential components in electrical distribution systems, acting as a bridge between the high voltage transmission lines and the low voltage distribution networks. These transformers are designed to step down voltage levels to make electricity usable for residential and commercial applications. Their reliability and efficiency play a crucial role in ensuring that power is delivered safely and consistently.
In particular, the 2500 kVA transformer is a significant player in this category. It is often utilized in various industrial settings where large amounts of power are required. The capacity of 2500 kVA allows it to support heavy loads, making it an ideal choice for factories, shopping malls, and other infrastructure with high energy demands. The design and construction of these transformers typically ensure longevity and minimal maintenance, which further enhances their appeal.
Benefits of Choosing a Chinese Manufacturer
China has emerged as a leading manufacturer of distribution transformers, including the 2500 kVA models. One of the primary reasons behind this is the high cost performance that these manufacturers offer. With advanced production techniques and economies of scale, Chinese manufacturers can produce transformers at competitive prices without compromising on quality. This makes them an attractive option for businesses looking to maximize their return on investment.
Type | Rating capacity (KVA) | Voltage combination(KV) | Off-load losses(W) | Load losses(W) | Off-load current (%) | Short-circuit voltage (%) |
SC13-30 | 30 | 6,6.3,6.6,10,11/0.4 | 150 | 710 | 2.3 | 4.0 |
SC13-50 | 50 | 6,6.3,6.6,10,11/0.4 | 215 | 1000 | 2.2 | 4.0 |
SC13-80 | 80 | 6,6.3,6.6,10,11/0.4 | 295 | 1380 | 1.7 | 4.0 |
SC13-100 | 100 | 6,6.3,6.6,10,11/0.4 | 320 | 1570 | 1.7 | 4.0 |
SC13-125 | 125 | 6,6.3,6.6,10,11/0.4 | 375 | 1850 | 1.5 | 4.0 |
SCB13-160 | 160 | 6,6.3,6.6,10,11/0.4 | 430 | 2130 | 1.5 | 4.0 |
SCB13-200 | 200 | 6,6.3,6.6,10,11/0.4 | 495 | 2530 | 1.3 | 4.0 |
SCB13-250 | 250 | 6,6.3,6.6,10,11/0.4 | 575 | 2760 | 1.3 | 4.0 |
SCB13-315 | 315 | 6,6.3,6.6,10,11/0.4 | 705 | 3470 | 1.1 | 4.0 |
SCB13-400 | 400 | 6,6.3,6.6,10,11/0.4 | 785 | 3990 | 1.1 | 4.0 |
SCB13-500 | 500 | 6,6.3,6.6,10,11/0.4 | 930 | 4880 | 1.1 | 4.0 |
SCB13-630 | 630 | 6,6.3,6.6,10,11/0.4 | 1070 | 5880 | 0.9 | 4.0 |
SCB13-630 | 630 | 6,6.3,6.6,10,11/0.4 | 1040 | 5960 | 0.9 | 6.0 |
SCB13-800 | 800 | 6,6.3,6.6,10,11/0.4 | 1210 | 6960 | 0.9 | 6.0 |
SCB13-1000 | 1000 | 6,6.3,6.6,10,11/0.4 | 1410 | 8130 | 0.9 | 6.0 |
SCB13-1250 | 1250 | 6,6.3,6.6,10,11/0.4 | 1670 | 9690 | 0.9 | 6.0 |
SCB13-1600 | 1600 | 6,6.3,6.6,10,11/0.4 | 1960 | 11700 | 0.9 | 6.0 |
SCB13-2000 | 2000 | 6,6.3,6.6,10,11/0.4 | 2440 | 14400 | 0.7 | 6.0 |
SCB13-2500 | 2500 | 6,6.3,6.6,10,11/0.4 | 2880 | 17100 | 0.7 | 6.0 |
Moreover, many Chinese manufacturers prioritize technological innovation. They are continuously improving their designs and incorporating the latest advancements in materials and engineering. This focus on quality ensures that customers receive durable and efficient products, which ultimately leads to reduced operational costs over time. Additionally, collaborating with a reputable Chinese manufacturer can provide access to comprehensive after-sales support, further enhancing the overall experience.
Key Considerations When Selecting a Transformer
Type | Rated power (KVA) | Voltage combination(KV) | Off-load losses(W) | Load losses(W) | Off-load current (%) | Short-circuit impedance (%) |
SC10-800 | 800 | 33,35,38/6,6.3,6.6,10,11 | 2200 | 9400 | 1.1 | 6.0 |
SC10-1000 | 1000 | Voltage combination(KV) | 2610 | 10800 | 1.1 | 6.0 |
SC10-1250 | 1250 | 6,6.3,6.6,10,11/0.4 | 3060 | 11900 | 1.0 | 6.0 |
SC10-1500 | 1500 | Voltage combination(KV) | 3600 | 15400 | 1.0 | 6.0 |
SC10-2000 | 2000 | 6,6.3,6.6,10,11/0.4 | 4130 | 18200 | 0.9 | 7.0 |
SC10-2500 | 2500 | Voltage combination(KV) | 4750 | 21800 | 0.9 | 7.0 |
SC10-3150 | 3150 | 6,6.3,6.6,10,11/0.4 | 5880 | 24500 | 0.8 | 8.0 |
SC10-4000 | 4000 | Voltage combination(KV) | 6860 | 29400 | 0.8 | 8.0 |
SC10-5000 | 5000 | 6,6.3,6.6,10,11/0.4 | 8180 | 34960 | 0.7 | 8.0 |
SC10-6300 | 6300 | Voltage combination(KV) | 9680 | 40800 | 0.7 | 8.0 |
SC10-8000 | 8000 | 6,6.3,6.6,10,11/0.4 | 11000 | 46060 | 0.6 | 9.0 |
SC10-10000 | 10000 | Voltage combination(KV) | 12660 | 56500 | 0.6 | 9.0 |
SC10-12500 | 12500 | 6,6.3,6.6,10,11/0.4 | 15400 | 64600 | 0.5 | 9.0 |
SC10-16000 | 16000 | Voltage combination(KV) | 18900 | 76000 | 0.5 | 9.0 |
SC10-20000 | 20000 | 6,6.3,6.6,10,11/0.4 | 22400 | 85500 | 0.4 | 10.0 |
When selecting a distribution transformer, especially a 2500 kVA model, it’s crucial to consider several factors to ensure optimal performance. First and foremost, evaluate the specific power requirements of your application. Understanding load characteristics—such as peak demand and power factor—will help in choosing the right transformer that meets your needs without overspending.
Another important aspect is the transformer’s efficiency ratings. A higher efficiency translates to lower energy losses, which can significantly impact long-term operational costs. It’s also advisable to check for compliance with international standards, as this indicates reliability and safety. By taking these considerations into account, businesses can make informed decisions that lead to better outcomes in their energy management strategies.